CSB UPS12580 F2 - sealed lead acid accumulator with VRLA/AGM technology (the electrolyte is bound in a glass fleece), product of Hitachi Chemical Energy Technology Co. Ltd., Taiwan. Very good price/performance ratio. CSB GP batteries are characterized by a high quality standard of materials and workmanship. Typical properties are cyclic resistance, deep discharge resistance. The service life is about 4 to 6 years at 50% D.O.D. In cyclic operation, the charging voltage is 14.4 V – 14.9 V (at +25°C), in standby mode, the charging voltage is 13.5 V – 13.8 V (at +25°C).
Main applications: backup power supply for control panels and sirens of electronic security systems (ESS), into electronic fire-fighting systems (FPS), into back-up power supplies (UPS), for telecom applications etc. The battery can be used, e.g. in a backup power supply AWZ 230.
Specifications and technical parameters :
Terminal voltage: 12 V nom., 13.5 V to 13.8 V (charged and unloaded battery at +25°C)
Nominal capacity: 9 Ah at +25°C, 7.7 Ah at 0°C, 6.3 Ah at -10°C
Capacity Ah: 9 Ah/10 hrs. at Idisch. 0.88 A (end voltage 1.75V per cell/ 10.5V per accu)
Total energy stored: 108 Wh (at +25°C)
Initial charging current: 3.75 A / 2 hrs.
Recommended charging current: 0.9 A /10 hrs. (at +25°C)
* Recommended holding current (0,01C): 90 mA /unlimited (at -20°C to +55°C)
Recommended continuous discharge current: 0.45 A /20 hrs., 0.88 A /10 hrs., 1.7 A /5 hrs. (end voltage 1.75V per cell/ 10.5V per accu)
Short-term discharge current: 130 A / 5 sec.
Internal resistance: cca 13 mΩ
Capacity drop by self-discharge: approx. 3% of capacity (Ah)/month
Medium lifetime: 5 years (use in stand-by mode, charging in "float" mode to end voltage 13.5 V to 13.8 V at +25°C)
Operating temperature: -15°C to +50°C
Type and size of output terminals: Faston F2, 6.35 mm
Dimensions: 151 x 65 x 98 mm (l x w x h)
Weight: 2,8 kg
Delivery time: cca 1 week (on request)
* The holding charge current is dependent on the application in which the battery operates. If the battery is used in a backup power supply, this usually allows you to set the amount of current for continuous maintenance charging (usually 0,01 to 0,02C) and/or current for backup mode (after power failure, the power supply runs on the battery, after the power is re-started, the battery is charged with 0.1 C to full capacity and then charged with holding pulse current 0,01 to 0,02C).